Interlock kit vs transfer switch: connecting a generator
An interlock kit and a transfer switch both stop generator power flowing out to utility lines, called backfeed, which can electrocute line workers. An interlock is a sliding plate on your main panel; a transfer switch moves chosen circuits or the whole panel to the generator. A qualified electrician fits either. With neither, use extension cords.
Key facts
| Fact | Value | Source |
|---|---|---|
| What backfeed is | Generator power flowing through a building's wiring into downed or de-energized utility lines | OSHA fact sheet |
| OSHA's stated rule of thumb | Use portable generators as standalone sources, or connect through a properly installed main breaker bypass or isolation connection | OSHA fact sheet |
| Who may make the connection (Honda manual) | A qualified electrician, isolating generator power from utility power, in line with all applicable laws and electrical codes | Honda EU2200i manual, p. 54 |
| Harm to utility workers | Honda warns backfeed may electrocute utility company workers or others who touch the lines during an outage | Honda EU2200i manual, p. 54 |
| Harm to the generator and house | The generator may explode, burn or cause fires when utility power is restored | Honda EU2200i manual, p. 54 |
| Utility workers' own rule on backfeed | Federal rules for power-line employers address possible voltage backfeed from cogeneration or the secondary system | 29 CFR 1910.269(w)(7), eCFR |
| How an interlock works | A mechanical sliding plate on the service panel stops the main breaker and the generator breaker being on together | Generac |
What is backfeeding a generator?
Backfeeding means generator power flows out through a building’s wiring into the utility lines. OSHA calls it “a hazardous condition” created when a temporary source, such as a generator, is connected to the damaged permanent system.
The danger is to people outside the house. Honda’s manual warns that backfeed “may electrocute utility company workers or others who contact the lines during a power outage.” Federal rules tell crews to treat lines as energized unless they have been deenergized by set procedures, but a backfeeding generator can energize a line before those steps finish.
It also hurts the owner. Honda says the generator “may explode, burn, or cause fires when utility power is restored.”
Why do you need an interlock kit or transfer switch?
Both devices stop the generator and the utility feeding the house at the same moment. OSHA says a generator connected to a building’s system must use a properly installed main breaker bypass so electricity cannot flow out into downed lines.
Honda puts it as a rule for owners. The connection “must isolate the generator power from utility power” and must follow all applicable laws and electrical codes.
OSHA leaves two options: run the generator as a standalone source, or connect it through a properly wired bypass or isolation connection.
What is the difference between an interlock kit and a transfer switch?
An interlock kit is a mechanical safety device on your service panel. Generac describes a sliding plate that blocks either the main breaker or the generator breaker from switching on while the other is active. You switch the main off, then the generator breaker on. Kits vary with the style of panel.
A transfer switch is a dedicated switch that moves the load from the utility to the generator. It comes in two forms. A selected-circuit transfer panel feeds a few chosen circuits. A whole-house manual transfer switch, such as Generac’s, feeds your entire load center and lets you switch off loads by hand to stay within the generator’s capacity.
| Extension cords | Interlock kit | Transfer switch | |
|---|---|---|---|
| Stops backfeed | Yes, nothing touches the house wiring | Yes, when installed correctly | Yes, when installed correctly |
| What it powers | Only what you plug in | Compatible panel circuits you switch on, within generator voltage and capacity | Selected circuits, or the whole load center with loads shed by hand |
| Who connects it | An instructed operator following the generator and appliance manuals | A licensed or qualified electrician | A licensed or qualified electrician |
| Building-wiring work | None | Yes | Yes |
| Code acceptance | Check local generator-use rules | Not accepted everywhere; confirm with your local authority | Generac recommends it for a code-compliant setup |
The practical split is circuit control. A selected-circuit panel locks in the circuits at install, so nobody overloads the generator by accident. An interlock or whole-house switch gives you every circuit in the panel and puts the load math on you. Know your generator’s watts first: see what size generator you need for a house and for a refrigerator. Check voltage too. A 120 V inverter generator such as Honda’s EU2200i cannot run 240 V circuits like a well pump or electric range.
Which should you choose?
- Small portable generator, a few essentials: extension cords. No install, no inspection of your panel.
- Portable generator, you want the furnace, fridge and lights wired in, and your inspector accepts interlocks for your panel: an interlock kit. It is the lighter install, and Generac says it suits smaller or occasional backup needs.
- Your jurisdiction rejects interlocks, or you want a code-compliant setup without panel-specific kits: a transfer switch. Generac points buyers who need that to its manual transfer switches.
- You want fixed circuits and no overload risk: a selected-circuit transfer panel.
Is a generator interlock legal?
It depends on your local electrical code and the inspector who enforces it. Generac states that interlock kits are not universally accepted in all jurisdictions and tells buyers to verify with the authority having jurisdiction. This page covers US sources. Outside the US, ask a registered electrician and your network operator.
Honda’s manual says the connection must be made by a qualified electrician and comply with all applicable laws and electrical codes. It adds that some areas require the generator to be registered with the local utility.
Call your building or electrical authority with two questions. Do they accept an interlock for your panel’s make and model, and do they require a permit? Get the answer from them, not from a retailer’s page.
What does OSHA say about utility workers and backfeed?
OSHA’s rules for power-line employers address backfeed directly. 29 CFR 1910.269(w)(7) says that where voltage backfeed is possible, from cogeneration sources or from the secondary system, employers must apply their rules for work on energized or de-energized lines.
That rule binds the utility, not you. It shows why crews cannot assume a line is dead because the power is out.
When should you use cords instead?
Use extension cords straight from the generator to the appliance if you have no installed interlock or transfer switch. This is the standalone use OSHA describes.
Keep the generator outdoors and away from the house, as covered in how far a generator should be from the house. Plan fuel for the run as well: see how long a generator can run.
Checklist before you connect a generator to a house
- Is the connection an interlock kit or transfer switch fitted by a qualified electrician?
- Did you ask your local authority and utility about permits and registration?
- Is the device made for your exact panel, and does your inspector accept it?
- Is the generator outside, with cords routed in a way that keeps doors and windows closed?
- Can you confirm the main breaker is off before starting the generator?
Frequently asked questions
Is a generator interlock kit legal?
Acceptance depends on your local electrical code and the inspector who enforces it. Generac notes interlock kits are not universally accepted in all jurisdictions and tells buyers to verify with the authority having jurisdiction. Honda's manual requires a qualified electrician and compliance with all applicable laws and electrical codes. Call your building or electrical authority with your panel's make and model before you buy.
What is backfeeding a generator?
Backfeed is generator power flowing out of a building and into utility lines. OSHA describes it as a hazardous condition created when a temporary source is connected to the damaged permanent system. It can energize lines that crews and neighbors assume are dead.
Can I plug my generator into a wall outlet?
No. OSHA says portable generators should be used as standalone sources unless connected through a properly wired bypass or isolation connection. A wall outlet is neither. Run extension cords from the generator to the appliance instead.
Do I need a permit to connect a generator to my house?
Permit rules depend on your local authority. Honda's manual adds that some areas require generators to be registered with the local utility, and tells owners to consult the utility or a qualified electrician first. Call both before work starts.
Does switching off the main breaker make it safe?
Not on its own. OSHA says a generator connected to a building's system must go through a properly installed main breaker bypass. An interlock kit or transfer switch fitted by an electrician is that bypass.
Sources
- Working Safely Around Downed Electrical Wires (fact sheet), Occupational Safety and Health Administration (OSHA) (accessed 2026-10-26)
- EU2200i / EU2200i Companion Owner's Manual, Honda Power Equipment, 2020 (accessed 2026-10-26)
- 29 CFR 1910.269, Electric power generation, transmission, and distribution, Electronic Code of Federal Regulations (accessed 2026-10-26)
- What is an interlock kit?, Generac Support (accessed 2026-10-27)
- Whole-house manual transfer switches for portable generators, Generac (accessed 2026-10-27)